Installation Instructions
The Modbus com interface need the libmodbus (http://libmodbus.org/) library to work.
Follow the steps below to set up your environment before compiling forte
1. libmodbus files should be placed in the following folder structure:
<libmodbushome>/include/modbus: include files
<libmodbushome>/lib: libmodbus.lib (windows) or libmodbus.so (posix)
2. When configuring forte project with CMake choose <libmodbushome> as FORTE_COM_MODBUS_LIB_DIR
3. forte.exe must be able to find the dynamic libmodbus library after build
- copy libmodbus.dll/so to folder with forte.exe or
- add libmodbus.dll/so to library include path
Parameter Documentation
Modbus Client (TCP)
At the moment the Modbus client can only be used for reading values from a Modbus server.
modbus[(protocol:)ip:port:pollFreqency:functionCode:(slaveId):readAddresses:sendAddresses(:responseTimeout:byteTimeout)]
- protocol: tcp (tcp is default)
- ip: 127.0.0.1 etc
- port: default is 502
- pollFrequency: polling frequency in milliseconds
- functionCode: 1 - Read Coils
2 - Read Discrete Inputs
3 - Read Holding Registers
4 - Read Input Register
- slaveId (optional): the slave id used by the modbus server (0xFF is standard)
- readAddresses: addresses can be specified between 0-65535
more than one address (max 100) can be specified using
+ comma for separate addresses 0,2,65500
+ dots for interval 5..10
+ combination 0,5..10,2,65500
- sendAddresses: addresses can be specified between 0-65535
if data is only read sendAddresses should be left empty
more than one address (max 100) can be specified using
+ comma for separate addresses 0,2,65500
+ dots for interval 5..10
+ combination 0,5..10,2,65500
- responseTimeout (optional): timeout in milliseconds to wait for a response (500ms is default)
- byteTimeout (optional): timeout in milliseconds between two consecutive bytes (500ms is default)
example: modbus[127.0.0.1:502:1000:3:1:0..3:]